F013 Powerflex 525. Inversor Powerflex 525 15hp 380 440v 24a 25bd024n104 Garantia SMO Powerflex 525 ground fault 013, drive damage after short? EDIT: Yes, bad drive now There are a few odd things going on here, but I'll start with.
Rockwell Automation Allen Bradley PowerFlex 525 AC drive Electrical from electricalconnection.com.au
There are a few odd things going on here, but I'll start with. PowerFlex 520 Series - F12 'HW Overcurrent' / F13 'Ground Fault' - All Drives! Looking for some insight
Rockwell Automation Allen Bradley PowerFlex 525 AC drive Electrical
Topic starter Mar 08, 2024 7:28 am (@click2electro) Member The PowerFlex 523/525 drives may generate an F013 Ground Fault or an F12 Overcurrent condition and for PowerFlex 527 fault can be FLT S16 GROUND CURRENT After replacing the drive, it works fine, but only for a couple.
25BD2P3N104 Allen Bradley VFD, 480V, 1HP, Powerflex 525. I swapped to a spare drive of the same type and still got the ground fault on run command The PowerFlex 525 drive may generate an = F013=20 Ground fault when P039 = [Torque=20 Perf Mode] is set to 1 -=20 SVC Mode, and the drive was not autotuned
PowerFlex 525 AC Drive WKB ELECTRIC. A Poweflex 525 drives a motor to extend the fingers open to hold the coil, to be shrink wrapped The Drive should have an encoder when in vector control mode for best regulation ( Parameter P039 [Torque Perf Mode] is set to 3 [Vector] ).The Rotate autotune must be performed, and.